    • Web server for device configuration and display of measured value curves

    • Up to 12 universal inputs, six digital inputs

    Specs at a glance

    Save cycle 1 s to 1 h
    Memory 128 MB internal memory, external SD card and USB stick
    Inputs Current, voltage, pulse/frequency and temperature
    Interfaces Ethernet, RS232/RS485 and USB
    Installation depth 158 mm
    Display 5.7" TFT screen
    Product / VersionPrice / pcs. in CADOrder code
    Input SignalCommunicationOperation Language Display1 to 34 to 1011+
    4x universalEthernet RJ45 + USBEnglish2,0851,9391,835 RSG35-BxA+AAC1
    French2,0851,9391,835 RSG35-BxA+ACC1
    Spanish2,0851,9391,835 RSG35-BxA+ADC1
    Portuguese2,0851,9391,835 RSG35-BxA+AGC1
    RS232/485 + Ethernet RJ45 + USBEnglish2,2402,0831,971 RSG35-BxB+AAC1
    French2,2402,0831,971 RSG35-BxB+ACC1
    Spanish2,2402,0831,971 RSG35-BxB+ADC1
    Portuguese2,2402,0831,971 RSG35-BxB+AGC1
    8x universalEthernet RJ45 + USBEnglish2,4262,2562,135 RSG35-CxA+AAC1
    French2,4262,2562,135 RSG35-CxA+ACC1
    Spanish2,4262,2562,135 RSG35-CxA+ADC1
    Portuguese2,4262,2562,135 RSG35-CxA+AGC1
    RS232/485 + Ethernet RJ45 + USBEnglish2,5812,4002,271 RSG35-CxB+AAC1
    French2,5812,4002,271 RSG35-CxB+ACC1
    Spanish2,5812,4002,271 RSG35-CxB+ADC1
    Portuguese2,5812,4002,271 RSG35-CxB+AGC1
    12x universalEthernet RJ45 + USBEnglish2,7672,5732,435 RSG35-DxA+AAC1
    French2,7672,5732,435 RSG35-DxA+ACC1
    Spanish2,7672,5732,435 RSG35-DxA+ADC1
    Portuguese2,7672,5732,435 RSG35-DxA+AGC1
    RS232/485 + Ethernet RJ45 + USBEnglish2,9222,7172,571 RSG35-DxB+AAC1
    French2,9222,7172,571 RSG35-DxB+ACC1
    Spanish2,9222,7172,571 RSG35-DxB+ADC1
    Portuguese2,9222,7172,571 RSG35-DxB+AGC1

    Prices valid until 30.11.2017 in CAD per unit (not including shipping and applicable sales taxes). See
    Endress+Hauser Terms and Conditions

  • Application

    The Ecograph T is the right solution for a wide range of applications such as: 

    • Quality and quantity monitoring in the water and wastewater industry
    • Monitoring of processes in power stations
    • Displaying and recording of critical process parameters
    • Tank and level monitoring
    • Temperature monitoring in metal working

    Function

    Data archiving with internal memory and separate SD card. Up to 30 internal limit values can be freely assigned to the channels. Limit value violations are saved and can additionally be indicated via up to 6 relays. Measured values can be saved in a maximum of four groups with different save cycles. Groups are selected via the jog/shuttle dial and displayed on the multicolored TFT display. The Essential Version of the Field Data Manager software is supplied with the product as standard. This software can be used to export the recorded data, save the data to an SQL database and visualize the data externally.

    Application Example

    graphic data manager Ecograph T RSG35 - Application example

    Ecograph T RSG35 records the temperature profile in a pipe.

  • Technical data

    Input values (universal input)
    Number of inputs 0/4/8/12
    Measured variables

    Current: 0 to 5/20 mA, 4 to 20 mA;

    Voltage: 0 to 1/5/10 V, 1 to 5 V, ±150 mV, ±1 V, ±10 V, ±30 V;

    Resistance thermometer (RTD): Pt46, Pt50, Pt100, Pt500, Pt1 000, Cu50, Cu53, Cu100;

    Thermocouples: Type J, K, T, N, L, D, C, B, S, R;

    Pulse input: max. 13 kHz

    Frequency input: 0 to 10 kHz

    Measured error

    ±0.1 % oMR (for current, voltage, resistance thermometer);

    ±0.01 % oMR (for frequency)

    Scan rate All channels within 100 ms
    Resolution 24 Bit
    Input values (digital input)
    Number of inputs 6
    Input frequency max. 25 Hz
    Pulse length

    Min. 20 ms (pulse counter);

    Min. 100 ms (control input)

    Input current max. 2 mA
    Input voltage max. 30 V
    Selectable functions

    Control input, ON/OFF message, pulse counter, operating time, message+operating time. Functions of the control input: start recording, screen saver on, external memory cycle, lock setup, time synchronization, limit value monitoring on/off

    Output values (auxiliary voltage output)
    Output voltage 24 V DC ± 15 %
    Output current max. 250 mA, short-circuit proof
    Output values (Relay output)
    Alarm relay 1 alarm relay with changeover contact
    Standard relay 5 relays with NO contact, e.g. for limit value messages (can be configured as NC contact).
    Relay switching capacity max. 3 A @ 250 V AC or 3 A @ 30 V DC
    Power supply
    Supply voltage

    ±24 V AC/DC (–10% / +15%) 50/60Hz;

    100 to 230 V AC (±10%) 50/60Hz

    Power consumption

    100 to 230 V: max. 35 VA;

    24 V: max. 24 VA

    Connection data interface/communication
    Standard USB, Ethernet
    Advanced options Serial RS232/RS485
    Operating conditions
    Ambient temp. range –10 to +50 °C (14 to 122 °F)
    Storage temperature –20 to +60 °C (–4 to +140 °F)
    Climate class To IEC 60654-1: Class B2
    Degree of protection Front-panel IP 65, NEMA 4; rear-panel IP 20
    EMC

    Interference immunity: as per IEC 61326 series (industrial environment)/ NAMUR NE 21;

    Interference emissions: as per IEC 61326-1 Class A

    Mechanical construction
    Weight Panel-mounted version approx. 2.2 kg (4.85 lbs)
    Materials

    Front frame: Zinc die cast

    Housing half-panels: sheet steel;

    Sight glass: Transparent Makrolon plastic

    Human interface
    Display multicolored TFT display (145 mm (5.7"))
    Languages German, English, Spanish, French, Italian, Dutch, Swedish, Polish, Portuguese, Czech, Russian, Japanese, Chinese
    Data storage
    Selectable save cycle

    1 / 2 / 3 / 4 / 5 / 10 / 15 / 20 / 30 s;

    1 / 2 / 3 / 4 / 5 / 10 / 30 min;

    1h

    Internal memory 128 MB
    Typ. recording length memory cycle 1 min.

    4 inputs: 359 weeks

    12 inputs: 127 weeks

     External memory  supported SD cards: 512 MB up to 32 GB

    Dimensions in mm (in inches)

    Panel installation

    graphic data manager Ecograph T RSG35 - Dimensions 1

    Installation according to instruction manual

    Desk top housing

     

    graphic data manager Ecograph T RSG35 - Dimensions 2

    Installation according to instruction manual

     

     

    Field housing IP65

    Installation according to instruction manual

    Electrical connection

    graphic data manager Ecograph T RSG35 - Electrical connections

    a) Supply voltage

    b) Digital in (D)

    c) Relay 1–6 max. 250 V/3 A

    d) 24V Out: max. 250 mA

    e) Analog inputs

    f) Type: Pt50, Pt100, Pt500, Pt1000, Cu50, Cu100

    g) 0 to 5 V, 0 to 10 V, +/– 10 V, +/– 30 V

    h) +/– 150 mV, +/– 1 V

    i) Type: J, K, T, N, L, D, C, B, A, S, R

    j) Impulse/ Frequence

    k) LOW = 0 to 7 mA; HIGH = 13 to 20 mA; Umax. = 2.5 V