Surge arresters

Surge arresters

HAW562 / HAW569 

from €42.-
Need help?

Info Hotline
+31 (35) 6 95 86 11

      • Field housing version
      • Application in Ex areas

      • High functional security (SIL2)

     

     

    Specs at a glance

    Design DIN rail mountable housing, field housing (HAW569)
    Approval ATEX II 2 (1) G
    Signal

    Power supply 24 V DC/AC, 230 V AC, current 0/4 to 20 mA, PROFIBUS® PA, RS485, PROFIBUS® DP

    Overvoltage protection HAW562 : DIN rail version

    Product / VersionPrice / pcs. in EUROrder code
    ApprovalApplication1 to 34 to 1011+
    Non-hazardous areaMeasuring signal 0/4-20mA, PFM,PA,FF91,-85,-80,- HAW562-AAA
    Supply voltage 10-55V48,-45,-42,- HAW562-AAB
    Supply voltage 90-230V48,-45,-42,- HAW562-AAC
    Communication RS485, Modbus PROFIBUS DP107,-99,-94,- HAW562-AAD
    Protection module Prosonic FMU90109,-101,-96,- HAW562-AAE
    ATEX/IECEx II2(1)G Ex ia[ia Ga]IIC T6 Gb + CSA C/US IS Cl I, Div. 1, Grp.A,B,C,D T6...T4Measuring signal 0/4-20mA, PFM,PA,FF103,-95,-90,- HAW562-8DA

    Overvoltage protection for installation on a field housing HAW569

    Product / VersionPrice / pcs. in EUROrder code
    ApprovalHousingVersion1 to 34 to 1011+
    Non-hazardous areaLead through version M20Measurement signal126,-118,-111,- HAW569-AA2B
    ATEX/IECEx II2(1)G Ex ia[ia Ga]IIC T6 GLead through version M20Measurement signal138,-128,-121,- HAW569-DA2B
    ATEX/IECEx II2G Gb Ex d IIC T6 + CSA C/US XP, DIP I,II,III/1+2/A-GScrew in version cable gland M20Measurement signal+power(0-66V+80-230V)158,-147,-139,- HAW569-CB2C

    Accessories

    Product / VersionPrice / pcs. in EUROrder code
    Earthing ring-set HAW569 M20 for sensors with non conductive housing earthing ring, lock nut, flat plug13,52 51006420
    Protective housing for surge arresters with build in top hat rail, earth lug GORE-TEX membrane, 2 sealable screws and 4 plastic cable glands M20; aluminium diecast housing, 100x160mm, epoxy powder coating, IP66/NEMA 4X.87,98 51003750
    Mounting bracket for wall-/pipe mount. of protective housing surge arresters, pipe diameter 25-140mm43,98 51003773

    Prices valid until 06.30.2020 in EUR per unit (not including shipping and applicable sales tax). See
    Endress+Hauser Terms and Conditions

  • Application

    The surge arrester is used for limiting high voltages in signal cables of 0/4 to 20 mA, PROFIBUS® PA and PFM signal, for limiting high voltages in bus systems like PROFIBUS® DP and RS485, in ultrasonic sensors and low voltage instrumentation supply cables.

    Function

    Protection of supply to instrumentation, signal cables and components from overvoltage surges – created by lightning strikes or switch sequences for example.

    Operation of power supply protection units: Using the impedance-free connection of the protection unit interference voltage drops cannot be introduced on the power lines.

    Operation of signal cable protection units: protection steps within the unit guarantee high compatibility with the system to be protected.

    Application example

    a) Capacity

    b) Linearization

    c) Level

  • Technical data HAW562

      HAW562-AAA HAW562-AAB HAW562-AAC HAW562-AAD HAW562-AAE HAW562-8DA
    Supply voltage
    Nominal voltage 24 V 60 V 230 V 5 V 12 V DC1)
    80 V DC2)
    24 V
    Max. continuous voltage 33 V DC
    23.3 V AC
    75 V 255 V 6 V DC
    4.2 V AC
    15 V DC1)
    180 V DC2)

    33 V DC
    23.3 V AC

    Current consumption
    Nominal current [IL] 1.0 A 25 A 25 A 1.0 A 0.45 A1)
    3 A2)
    500 mA at 
    Tamb = 80 °C (176 °F)
    C2 nominal discharge current [In] (8/20) per line 10 kA 2 kA 3 kA 10 kA 10 kA 5 kA
    C2 nominal discharge current [In] (8/20) total 20 kA 4 kA 5 kA 20 kA 20 kA 10 kA
    D1 lightning surge current [Iimp] (10/350) per line 2.5 kA - - 2.5 kA 2.5 kA 1 kA

    D1 lightning surge current [Iimp] (10/350) total

    9 kA - - 9 kA 7.5 kA 2 kA
    Voltage protection level
    Line/line ≤52 V at Iimp L-N: ≤400 V L-N: ≤1250 V ≤25 V - ≤52 V
    Line/PG ≤550 V at Iimp L/N-PE:
    ≤730 V
    L/N-PE:
    ≤1500 V
    ≤550 V ≤600 V ≤1400 V
    Response times
    Line/line   L-N: ≤25 ns L-N: ≤25 ns - ≤1 ns ≤1 ns
    Line/PG - L/N-PE:
    ≤100 ns
    L/N-PE:
    ≤100 ns
    - ≤100 ns ≤100 ns
    Capacitance
    Line/line ≤1,0 nF - - ≤25 pF - ≤0.8 nF
    Line/PG ≤25 pF - - ≤25 pF - ≤16 pF
    General
    SPD class Type 1 P1 Type 3 P3 Type 3 P3 Type 1 P1 Type 1 P1 Type 1 P1
    Limit frequency 7.8 MHz - - 100 MHz 2 MHz1)
    15 MHz2)
    7.7 MHz (50 Ω)
    3.2 MHz (100 Ω)
    Series impedance per line 1.0 Ω - - 1.0 Ω 1.8 Ω1)
    directly connected3)
    1.0 Ω
    Maximum line side overcurrent protection - 25 A gL/gG
    or B 25 A
    25 A gL/gG
    or B 25 A
    - - -

    1) Terminal 4
    2) Terminal 2
    3) Terminal 1+2

    Technical data HAW569

      HAW569-AA2B HAW569-DA2B HAW569-CB2C
    Supply voltage
    Nominal voltage 24 V 24 V 24 V Signal
    120 V / 230 V Power supply
    Maximum continuous voltage 24.5 V AC
    34.8 V DC
    24.5 V AC
    34.8 V DC
    22.6 V AC Signal
    255 V AC Power supply;
    32 V DC Signal
    255 V DC Power supply
    Current consumption
    Nominal current [IL] 0.5 A 0.5 A 0.55 A at 80 °C (176 °F)
    C2 nominal discharge current [In] (8/20) per line 10 kA 5 kA -
    C2 nominal discharge current [In] (8/20) total 10 kA 10 kA 10 kA
    C2 nominal discharge current [In] (8/20) shielding – PG 20 kA - -
    Nominal discharge current (8/20) L–N [In] - - 3 kA
    Total discharge current (8/20) L+N–PE [Itotal] - - 5 kA
    D1 lightning surge current [Iimp] (10/350) line – PG - - 1 kA
    D1 lightning surge current [Iimp] (10/350) total - - -
    Voltage protection level
    Line/line at In C2 ≤65 V ≤55 V ≤58 V
    Line/PG at In C2 ≤650 V ≤1100 V ≤900 V
    Shielding/PG at In C2 ≤650 V - -
    Line/line at 1 kV/μs C3 ≤50 V ≤49 V ≤50 V
    Line/PG at 1 kV/μs C3 ≤500 V ≤1000 V ≤850 V
    Line/line at 1 kV/μs C3 ≤600 V - -
    L–N - - ≤1.4 kV
    L/N–PE - - ≤1.5 kV
    Capacitance
    Line/line ≤400 pF ≤850 pF ≤25 pF
    Line/PG ≤20 pF ≤15 pF ≤15 pF
    General
    SPD class Type 2 P1 Type 2 P1 Type 2 P2
    Limit frequency 14 MHz 7 MHz -
    Series impedance per line 2.2 Ω 1.8 Ω -
    Maximum line side overcurrent protection - - 16 A gL/gG or B 16 A

    Dimensions (in mm)

    HAW562

    1) HAW562-AAA, -AAD, -AAE, -8DA

    2) HAW562-AAB, -AAC

    3) HAW562-AAB, -AAC: +0.5 mm

     

    Installation according to operation instructions

    HAW569-AA2B, -DA2B (lead-through version)

    Installation according to operation instructions

    HAW569-CB2C (screw-in version)

    Installation according to operation instructions

    Electrical connection HAW562

    HAW562-AAA, -AAD, -8DA

    a) protected

    HAW562-AAB, -AAC

    a) protected

    HAW562-AAE

    a) protected

    Electrical connection HAW569

    HAW569-AA2B (non-Ex lead-through version)

    a) protected

    b) Shield

    HAW569-DA2B (Ex ia lead-through version)

    a) protected

    HAW569-CB2C (Ex d screw-in version)

    a) protected

  • More documents for HAW562
    More documents for HAW569
  • Protective housing
    With integrated DIN rail for mounting up to four HAW56x units
    Integrated DIN top hat rail
    ground connection
    GORE-TEX® filter
    2 lead seal screws and 4 plastic cable glands M20 × 1.5
    material: Pressure die cast aluminium, epoxy coated, ingress protection to IP 66/NEMA 4x

    Dimensions (in mm)