Space-saving single/dual channel version
-
Can be used up to SIL3
-
Bidirectional HART® transmission
Specs at a glance
Certificates ATEX II (1) GD EEx ia IIC/IIB
ATEX II (1) GD EEx ib IIC/IIB
HART® communication Built-in resistance for HART® communication 232 Ω Version Optional dual-channel version Signal transmission - From non-Ex to Ex-areas
- From Ex to non-Ex areas
Passive Barrier RB223
Product / Version Price / pcs. in SGD Order code Approval Channel Transmission direction 1 to 3 4 to 10 11+ Non-hazardous area 1x LPS hazardous area to non-hazardous area 211.- 201.- 190.- RB223-A1A LPS non-hazardous to hazardous area 211.- 201.- 190.- RB223-A1B 2x LPS hazardous area to non-hazardous area 307.- 291.- 276.- RB223-A2A LPS non-hazardous to hazardous area 307.- 291.- 276.- RB223-A2B ATEX / FM / CSA 1x LPS hazardous area to non-hazardous area 233.- 221.- 210.- RB223-x1A LPS non-hazardous to hazardous area 233.- 221.- 210.- RB223-x1B 2x LPS hazardous area to non-hazardous area 328.- 312.- 296.- RB223-x2A LPS non-hazardous to hazardous area 328.- 312.- 296.- RB223-x2B Accessories
Product / Version Price / pcs. in SGD Order code Housing Field, R4 182x180x165, 5xM20, PC Protection housing Minitec. Synthetic housing with transparent cover. Protection IP66. 4x22.5mm / 2x45mm. Usage: FTL825. 137.53 52010132 Prices valid until 31.05.2018 in SGD per unit (not including shipping and applicable sales tax). See
Endress+Hauser Terms and ConditionsPeople who bought this also watched
-
-
Application
The RB223 isolator can be used to galvanically isolate active signal circuits (0 to 20 mA) in three applications:
- Transmission from non-Ex to Ex areas e.g for active adjusters,
controllers or indicators - Transmission from Ex to non-Ex areas for connection of active,
intrinsically safe circuits to the PLC - Transmission from Ex to non-Ex areas for supply of intrinsically safe transmitters with non-intrinsically safe transmitter power supply
Function
The passive isolator transmits signal circuits from the input to the output by galvanic isolation. A HART® signal is also transmitted. The device is optionally available with intrinsically safe input/ output. The device is loop-powered and does not need any additional supply voltage of its own.
Application Example
a) Ex area
b) NonEx area
c) Valve, actuator, display
d) Active
e) Passive
f) Process transmitter
g) 2-wire device (sensor, actuator)
h) 4-wire device (sensor, actuator)
i) Power supply
- Transmission from non-Ex to Ex areas e.g for active adjusters,
-
Technical data
Current transmission direction Non-Ex → Ex; InputFunction range 0 to 40 mA (to 22 mA for specified accuracy) Effective voltage Max. < 26 V for specified accuracy Short circuit current Imax = 100 mA Limiting voltage Umax = 30 V Current transmission direction Non-Ex → Ex; OutputFunction range 0 to 40 mA (to 22 mA for specified accuracy), max. current depends on load Load Load resistance max. 0 to 600 Ω Type of protection Intrinsically safe according to ATEX: - Max. voltage: Uo ≤ 28 V
- Max. current: Io ≤ 93 mA
- Max. power: Po ≤ 660 mW
Current transmission direction Ex → Non-Ex; InputFunction range 0 to 40 mA (to 22 mA for specified accuracy) Type of protection Intrinsically safe according to ATEX: - Max. voltage: Ui ≤ 30 V
- Max. current: Ii ≤ 100 mA
- Max. power: Pi ≤ 750 mW
Current transmission direction Ex → Non-Ex; OutputFunction range 0 to 40 mA (to 22 mA for specified accuracy), max. current depends on load Load Load resistance max. 0 to 600 Ω Galvanic isolationTest voltage >1.5 kV AC between input and output
>1.5 kV AC between the channels
Power supplyStarting current Own consumption < 50 µA Voltage drop <(1.9 V + 400 Ω × current loop) for nonEx → Ex
<(3.9 V + 120 Ω × current loop) for Ex → nonEx
Power loss <0.2 W at 20 mA (per channel) without HART®
<0.3 W at 20 mA (per channel) with HART®
AccuracyCurrent transmission < ±10 µA + 0.15 % from measured value Temperature drift ≤ ±0.01 % / 10 K Operating conditionsAmbient temp. –20 to +60 °C (–4 to +140 °F) Storage temperature –20 to +80 °C (–4 to +176 °F) Climate class To IEC 60 654-1 class B2 Relative humidity <95 % without condensation EMC Interference immunity to IEC 61 326 (industry) and NAMUR NE21 Mechanical constructionDimensions
(W × H × D)22.5 × 96 × 112 (0.89" × 3.78" × 4.33") for DIN rail to IEC 60 715 TH35 Weight Approx. 150 g (5.29 oz.) GeneralCommunication HART® protocol: bi-directional possible Frequency response 650 Hz for 500 Ω load for nonEx -> Ex 1300 Hz for 500 Ω load for Ex -> nonEx ApprovalsEx approvals ATEX II (1) GD [EEx ia] IIC/IIB
ATEX II (1) GD [EEx ib] IIC/IIB
SIL Can be used up to SIL3 Dimensions in mm (inches)
Installation according to instruction manual
Electrical connection
Connection RB223, Ex → Non-Ex 2 channel
a) Non-Ex
b) channel 2
c) channel 1
Connection RB223, Non-Ex → Ex 2 channel
a) Non-Ex
b) channel 2
c) channel 1
-
More documents for RB223