Surge arresters

Surge arresters

HAW562 / HAW569 

from S$80.-
Need help?

Info-Hotline
+65-65668222

      • Field housing version
      • Application in Ex areas

      • High functional security (SIL2)

     

     

    Specs at a glance

    Design DIN rail mountable housing, field housing (HAW569)
    Approval ATEX II 2 (1) G
    Signal

    Power supply 24 V DC/AC, 230 V AC, current 0/4 to 20 mA, PROFIBUS PA, RS485, PROFIBUS DP

    Surge Arrester HAW562

    Product / VersionPrice / pcs. in SGDOrder code
    ApprovalApplication1 to 34 to 1011+
    Non-hazardous areaMeasuring signal 0/4-20mA, PFM,PA,FF168.-160.-151.- HAW562-AAA
    Supply voltage 10-55V89.-85.-80.- HAW562-AAB
    Supply voltage 90-230V89.-85.-80.- HAW562-AAC
    Communication RS485, Modbus PROFIBUS DP197.-187.-177.- HAW562-AAD
    ATEX/IECEx II2(1)G Ex ia[ia Ga]IIC T6 GbMeasuring signal 0/4-20mA, PFM,PA,FF189.-180.-170.- HAW562-8DA

    Surge arrester HAW569

    Product / VersionPrice / pcs. in SGDOrder code
    HousingApprovalVersion1 to 34 to 1011+
    Lead through versionNon-hazardous area0/4-20mA,PFM, PROFIBUS PA, FOUNDATION Fieldbus # Measurement signal233.-222.-210.- HAW569-AA2B
    ATEX/IECEx II2(1)G Ex ia[ia Ga]IIC T6 G0/4-20mA,PFM, PROFIBUS PA, FOUNDATION Fieldbus # Measurement signal255.-242.-229.- HAW569-DA2B
    Screw in version cable gland M20ATEX/IECEx II2G Gb Ex d IIC T60/4-20mA,PFM, PROFIBUS PA, FOUNDATION Fieldbus # Measurement signal+power(0-66V+80-230V)293.-278.-263.- HAW569-CB2C

    Accessories

    Product / VersionPrice / pcs. in SGDOrder code
    IP 66 protective housing for 4 HAW562162.49 51003750
    Mounting kit for IP 66 housing81.24 51003773
    Earthing ring kit for HAW56924.98 51006420

    Prices valid until 30.11.2017 in SGD per unit (not including shipping and applicable sales tax). See
    Endress+Hauser Terms and Conditions

  • Application

    The surge arrester is used for limiting high voltages in signal cables of 0/4 to 20 mA, PROFIBUS PA and PFM signal, for limiting high voltages in bus systems like PROFIBUS DP and RS485, in ultrasonic sensors and low voltage instrumentation supply cables.

    Function

    Protection of supply to instrumentation, signal cables and components from overvoltage surges – created by lightning strikes or switch sequences for example.

    Operation of power supply protection units: Using the impedance-free connection of the protection unit interference voltage drops cannot be introduced on the power lines.

    Operation of signal cable protection units: protection steps within the unit guarantee high compatibility with the system to be protected.

    Application example

    a) Capacity

    b) Linearization

    c) Level

  • Technical data HAW562

      HAW562-AAA HAW562-AAB HAW562-AAC HAW562-AAD HAW562-AAE HAW562-8DA
    Supply voltage
    Nominal voltage 24 V 60 V 230 V 5 V 12 V DC1)
    80 V DC2)
    24 V
    Max. continuous voltage 33 V DC
    23.3 V AC
    75 V 255 V 6 V DC
    4.2 V AC
    15 V DC1)
    180 V DC2)

    33 V DC
    23.3 V AC

    Current consumption
    Nominal current [IL] 1.0 A 25 A 25 A 1.0 A 0.45 A1)
    3 A2)
    500 mA at 
    Tamb = 80 °C (176 °F)
    C2 nominal discharge current [In] (8/20) per line 10 kA 2 kA 3 kA 10 kA 10 kA 5 kA
    C2 nominal discharge current [In] (8/20) total 20 kA 4 kA 5 kA 20 kA 20 kA 10 kA
    D1 lightning surge current [Iimp] (10/350) per line 2.5 kA - - 2.5 kA 2.5 kA 1 kA

    D1 lightning surge current [Iimp] (10/350) total

    9 kA - - 9 kA 7.5 kA 2 kA
    Voltage protection level
    Line/line ≤52 V at Iimp L-N: ≤400 V L-N: ≤1250 V ≤25 V - ≤52 V
    Line/PG ≤550 V at Iimp L/N-PE:
    ≤730 V
    L/N-PE:
    ≤1500 V
    ≤550 V ≤600 V ≤1400 V
    Response times
    Line/line   L-N: ≤25 ns L-N: ≤25 ns - ≤1 ns ≤1 ns
    Line/PG - L/N-PE:
    ≤100 ns
    L/N-PE:
    ≤100 ns
    - ≤100 ns ≤100 ns
    Capacitance
    Line/line ≤1,0 nF - - ≤25 pF - ≤0.8 nF
    Line/PG ≤25 pF - - ≤25 pF - ≤16 pF
    General
    SPD class Type 1 P1 Type 3 P3 Type 3 P3 Type 1 P1 Type 1 P1 Type 1 P1
    Limit frequency 7.8 MHz - - 100 MHz 2 MHz1)
    15 MHz2)
    7.7 MHz (50 Ω)
    3.2 MHz (100 Ω)
    Series impedance per line 1.0 Ω - - 1.0 Ω 1.8 Ω1)
    directly connected3)
    1.0 Ω
    Maximum line side overcurrent protection - 25 A gL/gG
    or B 25 A
    25 A gL/gG
    or B 25 A
    - - -

    1) Terminal 4
    2) Terminal 2
    3) Terminal 1+2

    Technical data HAW569

      HAW569-AA2B HAW569-DA2B HAW569-CB2C
    Supply voltage
    Nominal voltage 24 V 24 V 24 V Signal
    120 V / 230 V Power supply
    Maximum continuous voltage 24.5 V AC
    34.8 V DC
    24.5 V AC
    34.8 V DC
    22.6 V AC Signal
    255 V AC Power supply;
    32 V DC Signal
    255 V DC Power supply
    Current consumption
    Nominal current [IL] 0.5 A 0.5 A 0.55 A at 80 °C (176 °F)
    C2 nominal discharge current [In] (8/20) per line 10 kA 5 kA -
    C2 nominal discharge current [In] (8/20) total 10 kA 10 kA 10 kA
    C2 nominal discharge current [In] (8/20) shielding – PG 20 kA - -
    Nominal discharge current (8/20) L–N [In] - - 3 kA
    Total discharge current (8/20) L+N–PE [Itotal] - - 5 kA
    D1 lightning surge current [Iimp] (10/350) line – PG - - 1 kA
    D1 lightning surge current [Iimp] (10/350) total - - -
    Voltage protection level
    Line/line at In C2 ≤65 V ≤55 V ≤58 V
    Line/PG at In C2 ≤650 V ≤1100 V ≤900 V
    Shielding/PG at In C2 ≤650 V - -
    Line/line at 1 kV/μs C3 ≤50 V ≤49 V ≤50 V
    Line/PG at 1 kV/μs C3 ≤500 V ≤1000 V ≤850 V
    Line/line at 1 kV/μs C3 ≤600 V - -
    L–N - - ≤1.4 kV
    L/N–PE - - ≤1.5 kV
    Capacitance
    Line/line ≤400 pF ≤850 pF ≤25 pF
    Line/PG ≤20 pF ≤15 pF ≤15 pF
    General
    SPD class Type 2 P1 Type 2 P1 Type 2 P2
    Limit frequency 14 MHz 7 MHz -
    Series impedance per line 2.2 Ω 1.8 Ω -
    Maximum line side overcurrent protection - - 16 A gL/gG or B 16 A

    Dimensions in mm (inches)

    HAW562

    1) HAW562-AAA, -AAD, -AAE, -8DA

    2) HAW562-AAB, -AAC

    3) HAW562-AAB, -AAC: +0.5 mm

     

    Installation according to operation instructions

    HAW569-AA2B, -DA2B (lead-through version)

    Installation according to operation instructions

    HAW569-CB2C (screw-in version)

    Installation according to operation instructions

    Electrical connection HAW562

    HAW562-AAA, -AAD, -8DA

    a) protected

    HAW562-AAB, -AAC

    a) protected

    HAW562-AAE

    a) protected

    Electrical connection HAW569

    HAW569-AA2B (non-Ex lead-through version)

    a) protected

    b) Shield

    HAW569-DA2B (Ex ia lead-through version)

    a) protected

    HAW569-CB2C (Ex d screw-in version)

    a) protected

  • More documents for HAW562
    More documents for HAW569
  • Protective housing
    With integrated DIN rail for mounting up to four HAW56x units
    Integrated DIN top hat rail
    ground connection
    GORE-TEX® filter
    2 lead seal screws and 4 plastic cable glands M20 × 1.5
    material: Pressure die cast aluminium, epoxy coated, ingress protection to IP 66/NEMA 4x

    Dimensions (in mm)