Electronic acquisition, display, recording, analysis, remote transmission and archiving of analog and
digital input signals - Web server for device configuration and display of measured value curves
-
4 mathematics channels
Specs at a glance
Save cycle 1 s to 1 h Memory 128 MB internal memory, external SD card and USB stick Inputs Current, voltage, pulse/frequency and temperature Interfaces Ethernet, RS232/RS485 and USB, Modbus RTU/TCP slave Installation depth 158 mm Display 5.7" TFT screen Ecograph T RSG35
Product / Version Price / pcs. in SGD Order code Input Signal Communication Operation Language Display 1 to 3 4 to 10 11+ 4x universal Ethernet RJ45 + USB English 2,289.- 2,174.- 2,060.- RSG35-BxA+AAC1 Japanese 2,289.- 2,174.- 2,060.- RSG35-BxA+ALC1 Spanish 2,289.- 2,174.- 2,060.- RSG35-BxA+ADC1 RS232/485 + Ethernet RJ45 + USB English 2,459.- 2,336.- 2,213.- RSG35-BxB+AAC1 Japanese 2,459.- 2,336.- 2,213.- RSG35-BxB+ALC1 Chinese simplified 2,459.- 2,336.- 2,213.- RSG35-BxB+AKC1 8x universal Ethernet RJ45 + USB English 2,663.- 2,530.- 2,397.- RSG35-CxA+AAC1 Japanese 2,663.- 2,530.- 2,397.- RSG35-CxA+ALC1 Chinese simplified 2,663.- 2,530.- 2,397.- RSG35-CxA+AKC1 RS232/485 + Ethernet RJ45 + USB English 2,833.- 2,691.- 2,550.- RSG35-CxB+AAC1 Japanese 2,833.- 2,691.- 2,550.- RSG35-CxB+ALC1 Chinese simplified 2,833.- 2,691.- 2,550.- RSG35-CxB+AKC1 12x universal Ethernet RJ45 + USB English 3,037.- 2,885.- 2,734.- RSG35-DxA+AAC1 Japanese 3,037.- 2,885.- 2,734.- RSG35-DxA+ALC1 Chinese simplified 3,037.- 2,885.- 2,734.- RSG35-DxA+AKC1 RS232/485 + Ethernet RJ45 + USB English 3,207.- 3,047.- 2,887.- RSG35-DxB+AAC1 Japanese 3,207.- 3,047.- 2,887.- RSG35-DxB+ALC1 Chinese simplified 3,207.- 3,047.- 2,887.- RSG35-DxB+AKC1 Prices valid until 31.12.2019 in SGD per unit (not including shipping and applicable sales tax). See
Endress+Hauser Terms and ConditionsIs this data manager not the perfect match for your application?
People who bought this also watched
-
-
Application
The Ecograph T is the right solution for a wide range of applications such as:
- Quality and quantity monitoring in the water and wastewater industry
- Monitoring of processes in power stations
- Displaying and recording of critical process parameters
- Tank and level monitoring
- Temperature monitoring in metal working
Function
Data archiving with internal memory and separate SD card. Up to 30 internal limit values can be freely assigned to the channels. Limit value violations are saved and can additionally be indicated via up to 6 relays. Measured values can be saved in a maximum of four groups with different save cycles. Groups are selected via the jog/shuttle dial and displayed on the multicolored TFT display. The Essential Version of the Field Data Manager software is supplied with the product as standard. This software can be used to export the recorded data, save the data to an SQL database and visualize the data externally.
Application Example
Ecograph T RSG35 records the temperature profile in a pipe.
-
Technical data
Input values (universal input)Number of inputs 0/4/8/12 Measured variables Current: 0 to 5/20 mA, 4 to 20 mA;
Voltage: 0 to 1/5/10 V, 1 to 5 V, ±150 mV, ±1 V, ±10 V, ±30 V;
Resistance thermometer (RTD): Pt46, Pt50, Pt100, Pt500, Pt1 000, Cu50, Cu53, Cu100;
Thermocouples: Type J, K, T, N, L, D, C, B, S, R;
Pulse input: max. 13 kHz Frequency input: 0 to 10 kHz
Measured error ±0,1 % oMR (for current, voltage, resistance thermometer);
±0,01 % oMR (for frequency)
Scan rate All channels within 100 ms Resolution 24 Bit Input values (digital input)Number of inputs 6 Input frequency max. 25 Hz Pulse length min. 20 ms Input current max. 2 mA Input voltage max. 30 V Selectable functions Control input, ON/OFF message, pulse counter, operating time, message+operating time.
Functions of the control input: start recording, screen saver on, external memory cycle, lock setup, time synchronization, limit value monitoring on/off
Output values (auxiliary voltage output)Output voltage 24 V DC ± 15 % Output current max. 250 mA, short-circuit proof Output values (Relay output)Alarm relay 1 alarm relay with changeover contact Standard relay 5 relays with NO contact, e.g. for limit value messages (can be configured as NC contact). Relay switching capacity max. 3 A @ 250 V AC or 3 A @ 30 V DC Power supplySupply voltage 100 to 230 V AC (±10%) 50/60Hz; ±24 V AC/DC (–10% / +15%) 50/60Hz Power consumption 100 to 230 V: max. 35 VA; 24 V: max. 24 VA Connection data interface/communicationStandard USB, Ethernet Advanced options Serial RS232/RS485; Modbus RTU/TCP Slave Operating conditionsAmbient temp. range –10 to +50 °C Storage temperature –20 to +60 °C Climate class To IEC 60654-1: Class B2 Degree of protection Front-panel IP 65, NEMA 4; rear-panel IP 20 EMC Interference immunity: To IEC 61326 (industrial environment) / NAMUR NE 21; Interference emissions: To IEC 61326, Class A Mechanical constructionWeight Panel-mounted version approx. 2.2 kg Materials Front frame: Zinc die cast
Housing half-panels: sheet steel;
Sight glass: Transparent Makrolon plastic
Human interfaceDisplay multicolored TFT display (145 mm) Languages German, English, Spanish, French, Italian Data storageSelectable save cycle 1 / 2 / 3 / 4 / 5 / 10 / 15 / 20 / 30 s;
1 / 2 / 3 / 4 / 5 / 10 / 30 min;
1h
Internal memory 128 MB Typ. recording length memory cycle 1 min. 4 inputs: 359 weeks
12 inputs: 127 weeks
External memory supported SD cards: 512 MB up to 32 GB Dimensions in mm (inches)
Panel installation
Installation according to instruction manual
Desk top housing
Installation according to instruction manual
Field housing IP65
Installation according to instruction manual
Electrical connection
a) Supply voltage
b) Digital in (D)
c) Relay 1–6 max. 250 V / 3 A
d) 24 V Out: max. 250 mA
e) Analog inputs
f) Type: Pt50, Pt100, Pt500, Pt1000, Cu50, Cu100
g) 0...5 V, 0...10 V, +/– 10 V, +/– 30 V
h) +/– 150 mV, +/– 1 V
i) Type: J, K, T, N, L, D, C, B, A, S, R
j) Impulse/Frequence
k) LOW = 0...7 mA; HIGH = 13...20 mA; Umax. = 2.5 V
-