Space-saving single/dual channel version
-
Can be used up to SIL3
-
Bidirectional HART® transmission
Specs at a glance
Certificates ATEX II (1) GD EEx ia IIC/IIB
ATEX II (1) GD EEx ib IIC/IIB
HART® communication Built-in resistance for HART® communication 232 Ω Version Optional dual-channel version Signal transmission - From non-Ex to Ex-areas
- From Ex to non-Ex areas
Passive barrier RB223
Product / Version Price / pcs. in USD Order code Approval Channel Transmission direction 1 to 3 4 to 10 11+ Classified area 1x LPS hazardous area to non-hazardous area 220.- 204.- 193.- RB223-x1A LPS non-hazardous to hazardous area 220.- 204.- 193.- RB223-x1B 2x LPS hazardous area to non-hazardous area 305.- 284.- 269.- RB223-x2A LPS non-hazardous to hazardous area 305.- 284.- 269.- RB223-x2B Accessories
Product / Version Price / pcs. in USD Order code Housing Field, R4 182x180x165, 5xM20, PC Protection housing Minitec. Synthetic housing with transparent cover. Protection IP66. 4x22.5mm / 2x45mm. Usage: FTL825. 103.82 52010132 Prices valid until 31.12.2019 in USD per unit (not including shipping and applicable sales tax). See
Endress+Hauser Terms and ConditionsPeople who bought this also watched
-
-
Application
The RB223 isolator can be used to galvanically isolate active signal circuits (0 to 20 mA) in three applications:
- Transmission from non-Ex to Ex areas e.g for active adjusters, controllers or indicators
- Transmission from Ex to non-Ex areas for connection of active, intrinsically safe circuits to the PLC
- Transmission from Ex to non-Ex areas for supply of intrinsically safe transmitters with non-intrinsically safe transmitter power supply
Function
The passive isolator transmits signal circuits from the input to the output by galvanic isolation. A HART® signal is also transmitted. The device is optionally available with intrinsically safe input/ output. The device is loop-powered and does not need any additional Ex area supply voltage of its own.
Application Example
a) Ex area
b) Non-Ex area
c) Valve, actuator, display
d) Active
e) Passive
f) Process transmitter
g) 2-wire device (sensor, actuator)
h) 4-wire device (sensor, actuator)
i) Power supply
-
Technical data
Current transmission direction Non-Ex → Ex; InputFunction range 0 to 40 mA (to 22 mA for specified accuracy) Effective voltage Max. < 26 V for specified accuracy Short circuit current Imax = 100 mA Limiting voltage Umax = 30 V Current transmission direction Non-Ex → Ex; OutputFunction range 0 to 40 mA (to 22 mA for specified accuracy), max. current depends on load Load Load resistance max. 0 to 600 Ω Type of protection Intrinsically safe according to ATEX: - Max. voltage: Uo ≤ 28 V
- Max. current: Io ≤ 93 mA
- Max. power: Po ≤ 660 mW
Current transmission direction Ex → Non-Ex; InputFunction range 0 to 40 mA (to 22 mA for specified accuracy) Type of protection Intrinsically safe according to ATEX: - Max. voltage: Ui ≤30 V
- Max. current: Ii ≤100 mA
- Max. power: Pi ≤750 mW
Current transmission direction Ex → Non-Ex; OutputFunction range 0 to 40 mA (to 22 mA for specified accuracy), max. current depends on load Load Load resistance max. 0 to 600 Ω Galvanic isolationTest voltage >1.5 kV AC between input and output
>1.5 kV AC between the channels
Power supplyStarting current Own consumption < 50 µA Voltage drop <(1.9 V + 400 Ω × current loop) for nonEx → Ex
<(3.9 V + 120 Ω × current loop) for Ex → nonEx
Power loss <0.2 W at 20 mA (per channel) without HART®
<0.3 W at 20 mA (per channel) with HART®
AccuracyCurrent transmission < ±10 µA + 0.15 % from measured value Temperature drift ≤ ±0.01 % / 10 K Operating conditionsAmbient temp. –20 to +60 °C (–4 to +140 °F) Storage temperature –20 to +80 °C (–4 to +176 °F) Climate class To IEC 60 654-1 class B2 Relative humidity <95 % without condensation EMC Interference immunity to IEC 61 326 (industry) and NAMUR NE21 Mechanical constructionDimensions
(W × H × D)22.5 × 96 × 112 (0.89" × 3.78" × 4.33") for DIN rail to IEC 60 715 TH35 Weight Approx. 150 g (5.29 oz.) GeneralCommunication HART® protocol: bi-directional possible Frequency response 650 Hz for 500 Ω load for nonEx -> Ex 1300 Hz for 500 Ω load for Ex -> nonEx ApprovalsEx approvals ATEX II (1) GD [EEx ia] IIC/IIB
ATEX II (1) GD [EEx ib] IIC/IIB
SIL Can be used up to SIL3 Dimensions in mm (inches)
Installation according to instruction manual
Electrical connection
Ex → Non-Ex 2 channel
a) Non-Ex
b) channel 2
c) channel 1
Non-Ex → Ex 2 channel
a) Non-Ex
b) channel 2
c) channel 1
-
More documents for RB223