Input with two-wire loop power supplyand intrinsic safety option
-
Pump control function
-
Digital output with integration
Specs at a glance
Display 7-digit/14 segment multicolored Approval ATEX II (1) GD [EEx ia] IIC;
FM AIS I, II, III;
CSA (Ex ia) I, II, III optional
Standard Dimensions 96 × 96 mm (3.78" × 3.78") Relays 4 or 8 (optional) Function Linearization, pump control function, integration Output Optional 1 × analog output Process indicator RIA452
Product / Version Price / pcs. in USD Order code Approval Measuring Signal Output 1 to 3 4 to 10 11+ Non-hazardous area 0/4-20mA 4x relay SPDT limit 792.- 736.- 697.- RIA452-A111A11A 4x relay SPDT limit + 1x analogue U,I 851.- 792.- 749.- RIA452-A112A11A Universal U,I,R,RTD,TC 4x relay SPDT limit 887.- 825.- 780.- RIA452-A121A11A 4x relay SPDT limit + 1x analogue U,I 946.- 880.- 833.- RIA452-A122A11A ATEX II(1)GD(EEx ia)IIC / FM AIS I,II,III/1/ABCDEFG / CSA (Ex ia)I,II,III/1/ABCDEFG 0/4-20mA 4x relay SPDT limit 859.- 799.- 756.- RIA452-x111A11A 4x relay SPDT limit + 1x analogue U,I 918.- 854.- 808.- RIA452-x112A11A Accessories
Product / Version Price / pcs. in USD Order code Configuration kit TXU10- for PC-programmable devices. set-up programme+interface cable for PC with USB-Port. 4 pin plug + ReadWin2000 149.23 TXU10-AA Prices valid until 31.12.2019 in USD per unit (not including shipping and applicable sales tax). See
Endress+Hauser Terms and ConditionsPeople who bought this also watched
-
-
Application
The RIA452 process display interprets and displays process signals with high resolution and accuracy. It can also be used to automate control tasks via limit values or analogue and digital outputs.
Function
Up to eight presettable relays monitor the measured value for any infringement (undershooting/overstepping) of the preset limit values. Further operation modes for the relays are sensor or device errors, batch and pump control functions (e.g. alternating pump control). The scalable analog output offers wide options to transfer the input signal: zoom function, linearization, offset, inverting and signal conversion (conversion in-/output). The optional impuls output offers the possibility to create integrated process values. Simple setting up using a serial interface and PC programme or manually using the configurating dial on the front of the unit.
Application example
-
Technical data
InputAnalog input 1 × 0/4 to 20 mA (impedance 5 Ω) Universal input 0/4 to 20 mA, 0 to 5 mA, ±40 mV, ±150 mV, ±600 mV, ±2,5 V, 0 to 10 V, 0 to 5 V, ±10 V, 30 to 3000 Ω resistance thermometer Pt100/500/1000, Cu50/100, Pt50 thermocouple types J, K, T, N, B, S, R to IEC 584; D, C to ASTM E998; L to DIN 43710, GOST
Digital input 4×, max. 10 Hz Accuracy 0.1 % of the measurement range end value OutputTransmitter supply 24 V DC, 250 mA, on option intrinsically safe 1 × 24 V DC, 22 mA in addition Analog output 1 × 0/4 to 20 mA, 0 to 10 V DC Output impedance Max. ≤ 600 Ω Digital output 1 × open collector passive 12.5 kHz 4 × relays (changeover contact), 250 V AC/30 V DC, 3-A;
expandable to 8 relays (option)
Linearity ≤0.1 % of the measurement range end value Operating conditionsAmbient temperature –20 to +60 °C (–4 to 140 °F) Storage temperature –30 to +70 °C (–22 to 158 °F) Climatic class To IEC 60 654-1 class B2 bedewing is forbidden EMC Interference immunity to IEC 61326 (industrial environment) and NAMUR NE 21; interference emissions to IEC 61326 Class A Ingress protection Front IP 65, Terminals IP 20 Power supplySupply voltage 90 to 250 V AC, 50/60 Hz
20 to 36 V DC / 20 to 28 V AC, 50/60 Hz
Mechanical constructionElectrical connection Plug on screw terminals, size 1.5 m² solid, 1.0 mm² multi with ferrule Materials used Housing front: ABS plastic, electro-plated
Housing casing: PC10GF plastic
User interfaceDisplay 7 digit 14-segment LC-display in white (10 mm / 0.39”);
engineering unit with 9 × 77 Dot Matrix display;
42-parts bargraph in yellow with over- and under range in red;
limit value markings in yellow;
status display
Range of display –99999 to +99999 Operation via Jog-Shuttle or using RS232 and PC software ReadWin® 2000 FunctionsFeatures Linearization with 32 points, elapsed hour indicator, alternating pump control, tendency analysis, batch-function, integration, min/max value storage ApprovalsEx approval ATEX II (1) GD [EEx ia] IIC
FM AIS I, II, III/1/ABCDEFG
CSA (Ex ia) I, II, III/1/ABCDEFG
Dimensions in mm (inches)
Installation according to instruction manual
Electrical connection
Current input
a) Current input (Clamps 12 and 82 are linked internally)
b) Loop power supply Max. 22 mA Input 0 to 20 mA
c) Input 0 to 20 mA
d) Relay output
e) Relay 1-8: 250 V AC/ 30 V DC
f) Analog output 0 to 20 mA, 0 to 10 V DC
g) Loop power supply 24 V, <= 250 mA
h) Digital inputs to DIN 19240
i) Digital output, passive open collector max. 24 V, 200 mA
Universal input
a) Current input 0 to 20 mA
b) Voltage input +/– 1 V
c) Voltage input +/– 30 V
d) Thermocouples
e) RTD 4-wire
f) RTD 3-wire
-
More documents for RIA452