- Bright, backlit LC indicator with bar graph, diagnostic symbols and plain text field
- Listener mode for up to 8 analog channels or digital statuses
- Optional aluminum housing for Ex applications
Specs at a glance
Communication and data processing FOUNDATION fieldbus™ or PROFIBUS® PA Degree of protection IP 67, NEMA 4X Approvals ATEX Ex ia, Ex nA;
FM IS, NI;
CSA IS, NI
Fieldbus Indicator RID14
Product / Version Price / pcs. in ZAR Order code Approval Communication 1 to 3 4 to 10 11+ Non-hazardous area FOUNDATION Fieldbus 9.044,- 8.140,- 7.416,- RID14-AA3C1 PROFIBUS PA 9.044,- 8.140,- 7.416,- RID14-AA3C2 ATEX II1G Ex ia IIC T6 FOUNDATION Fieldbus 9.900,- 8.910,- 8.118,- RID14-BA3C1 PROFIBUS PA 9.900,- 8.910,- 8.118,- RID14-BA3C2 Fieldbus Indicator RID16
Product / Version Price / pcs. in ZAR Order code Approval Communication Housing 1 to 3 4 to 10 11+ Non-hazardous area FOUNDATION Fieldbus Plastics, glass fiber reinforced 8.071,- 7.263,- 6.618,- RID16-AA1A1 PROFIBUS PA Plastics, glass fiber reinforced 8.071,- 7.263,- 6.618,- RID16-AA1A2 ATEX II2G Ex ia IIC T6 FOUNDATION Fieldbus Alu 10.178,- 9.160,- 8.346,- RID16-BA2A1 PROFIBUS PA Alu 10.178,- 9.160,- 8.346,- RID16-BA2A2 Prices valid until 31.05.2018 in ZAR per unit (not including shipping and applicable sales tax). See
Endress+Hauser Terms and ConditionsPeople who bought this also watched
-
Application
The RID14/RID16 field indicators monitor measurement signals and display them with high resolution and accuracy. Due to the backlit display they permit universal installation and are particularly suitable for use in the field or in mobile rigs.
Function
The 8-channel indicator displays the measured values, calculated values and status information of the fieldbus users in a fieldbus network. In the listener mode, the device listens to the set fieldbus addresses and displays their specific values. Furthermore, values available on the bus can also be displayed via function block interconnection in the case of a FOUNDATION fieldbus™ indicator. The process value status is indicated by icons or as plain text on the measured value display. The plain text display makes it possible to display alphanumeric character combinations, such as the TAG. The device is powered by the fieldbus and can be used in hazardous areas up to temperature class T6.
Application example
System integration via PROFIBUS® PA
a) Visualization and monitoring e. g. P View, FieldCare and diagnostic software
b) PLC
c) Segment coupler
d) Up to 32 devices per segment
-
Technical data
Communication and data processingFOUNDATION fieldbus™ FOUNDATION fieldbus™ H1, IEC 61158-2
FDE (Fault Disconnection Electronic) = 0 mA
Data transmission rate: supported baud rate = 31.25 kBit/s
Signal coding = Manchester II
LAS (link active scheduler), LM (link master) function is supported
In acc. with IEC 60079-27, FISCO/FNICO
PROFIBUS® PA PROFIBUS® PA in accordance with EN 50170 Volume 2, IEC 61158-2 (MBP)
FDE (Fault Disconnection Electronic) = 0 mA
Data transmission rate: supported baud rate = 31.25 kBit/s
Signal coding = Manchester II
Connection data in accordance with IEC 60079-11 FISCO, Entity
Power supplySupply voltage Voltage is supplied via the fieldbus. U = 9 to 32 V DC, polarity-independent (max. voltage Ub = 35 V) Current consumption ≤11 mA Cable entry RID14: Thread M20, NPT½;
RID16: Thread M16, NPT½Operating conditionsAmbient temperature limits –40 to +80 °C (–40 to 176 °F)
The display can react slowly at temperatures < –20 °C (–4 °F).
The readability of the display is no longer guaranteed at temperatures < –30 °C (–22 °F).
Storage temperature –40 to +80 °C (–40 to 176 °F) Climate class According to IEC 60654-1, Class C Degree of protection IP67. NEMA 4X. Mechanical constructionMaterial RID14:
Housing: Die-cast aluminum AlSi10Mg with powder coating on polyester base;
optional: Stainless steel 1.4405;RID16:
Housing: Fiber-glass reinforced plastic PBT-GF30;
optional: Aluminum AlSi12Weight RID14:
Aluminum housing: approx. 1.6 kg (3.5 lb)
Stainless steel housing: approx. 4.2 kg (9.3 lb)RID16:
Plastic housing: approx. 500 g (1.1 lb)
Aluminum housing: approx. 1.7 kg (3.75 lb)Terminals Screw terminals for cables up to max. 2.5 mm2 (14 AWG) plus ferrule ApprovalsRID14 FM IS, CSA IS, ATEX Ex ia, ATEX Ex d IEC RID16 FM IS, IN, CSA IS, NI, ATEX Ex ia, ATEX Ex d IEC Dimensions (in mm)